Replace DC Power Supplies with AC Power Supplies
Time required: |
10 to 15 minutes |
Parts required: |
Replacement AC power supplies ordered from HPE |
Information required: |
|
Tools required: |
|
Support contact: |
See Support. |
HPE recommends using the Maintenance Window functionality within the HPE InfoSight portal to inform HPE Support of upcoming maintenance windows.
Refer to https://infosight.hpe.com/dashboards/nimble/wellness/maintenance-windows for more information.
You can disable automated support case generation during planned maintenance from the Manage Maintenance Windows page. After a maintenance window is set, no further communication with HPE Support is required.
Use this procedure to replace the DC power supply units (PSUs) on your HPE storage array or expansion shelf with AC PSUs.
One PSU can adequately power the array while the other PSU is being replaced.
The procedure is the same for all HPE Nimble Storage arrays.
Before you attempt to replace a power supply:
- Do not remove the PSU until you are ready to install the replacement
- Never unplug or unseat both PSUs at the same time
- Use only UL-approved power cords