Install an Expansion Shelf
When you activate the expansion shelf, there is a momentary pause in data services from the array. You might need to activate the expansion shelf during a maintenance window.
The chassis weighs over 41 kg (90 lb). Always use at least two people or a server lift when lifting the chassis.
The chassis weighs over 32 kg (70 lb). Always use at least two people or a server lift when lifting the chassis.
What you need for each expansion shelf:
- 19-inch four-post square-hole rack. If your rack has round holes, use the provided square-hole adapters
- Four rack units (4U) of space available in the 19-inch rack
- Phillips screwdriver (included)
- At least two SAS cables, 1 m or 3 m (two 1 m cables are included) rack
-
Before beginning, download and read the Release Notes, available on HPE InfoSight (https://infosight.hpe.com). If you do not have an HPE InfoSight account, click Create Account and provide the required information.
- The power supplies are 220V AC or 110V AC auto-detecting.
- This product is intended for installation in restricted-access locations only, such as a dedicated equipment room or an electrical closet.
Use this procedure to install an ES2-AFS2 expansion shelf, or up to six ES2-H expansion shelves and one ES2-AFS2 expansion shelf (for Adaptive Flash arrays), or up to two SF-ES2 expansion shelves (for Secondary Flash arrays).