Connect and Activate an ES2-H or SF-ES2 Expansion Shelf
- CSxxxx Adaptive Flash arrays require NimbleOS 3.6 or later for the ES2-H shelf
- SFxxx Secondary Flash arrays require NimbleOS 4.2 or later for the SF-ES2 shelf
To verify the number of expansion shelves supported and the NimbleOS version required, refer to the Array Configuration Matrix available on InfoSight: https://infosight.hpe.com
-
When you activate the expansion shelf, there is a momentary pause in data services from the array. You might need to activate the expansion shelf during a maintenance window.
-
When possible, larger capacity shelves should be added to their own path instead of being daisy chained to an end of an existing path. If this is not possible, add the shelves to the path with the smallest difference in capacity.
Use this procedure to connect and activate up to six ES2-H expansion shelves or up to two SF-ES2 expansion shelves, depending on the model of your HPE Nimble Storage array.