Replace a Failed Drive
Use this procedure to replace HDDs in your HPE storage array or expansion shelf.
Time required: |
5 to 10 minutes |
Parts required: |
Replacement drive ordered from HPE |
Information required: |
|
Tools required: |
|
Support contact: |
See Support. |
HPE recommends using the Maintenance Window functionality within the HPE InfoSight portal to inform HPE Support of upcoming maintenance windows.
Refer to https://infosight.hpe.com/dashboards/nimble/wellness/maintenance-windows for more information.
You can disable automated support case generation during planned maintenance from the Manage Maintenance Windows page. After a maintenance window is set, no further communication with HPE Support is required.
Before you attempt to replace the drive:
- Do not remove the failed drive until you are ready to install the replacement.
- The replacement drive must be the same type and size as the failed drive.
- Determine which drive to replace before making the
replacement.
To identify a failed drive:
- LEDs are solid red or off
- Event appears in the Events list
- Receipt of an alert email from the array
- Verify that the replacement drive matches the part shown on the RMA work order.